System composition and characteristics of wireless nuclear phase meter

Wireless nuclear phaser performance indicators:

● Accuracy: In-phase error ≤ 10°, different phases ≤ 15°

● Host power supply 9V±2V

● Collector power supply 7.5V±1.5V

● The distance between the collectors X, Y and the host's line-of-sight is less than or equal to 70 meters. ● The collector's voltage level is 0.22KV-500KV.

●Working temperature -35°C-50°C

●Scalable insulated operating lever: 600mm in the contracted state and 3000mm in the extended state

● Packing size: length × width × height) 650mm × 250mm × 100mm

● Product Weight: The host weighs approximately 0.3Kg and weighs approximately 5Kg.

★ Wireless Phase Analyzer System Composition and Features

The test system consists of: host (receiving), X collector (emission), Y collector (emission), needle type and hook type two collection heads, and flexible insulating operating levers. (Accessories include aluminum alloy boxes, spare batteries, special calibration test clips with plugs).

The system uses digital circuits, complete functions, low power consumption, and normal use can replace the battery once a year (because of ordinary battery natural discharge). When the X and Y collector or main unit power supply voltage is low, the host screen has a low voltage alarm display.

★ High-pressure nuclear phase analyzer is safe and reliable

The X and Y collectors send the acquired voltage phase signals to the host through wireless signals, and have reliable high-voltage electrical safety isolation. All digital circuits are used in this product, which has strong anti-interference and stable and accurate data.

★ Convenient and quick

The X and Y collectors are easy to use and the host has an automatic shutdown feature. The wireless phaser insulation rod adopts retractable pull rods, no connection is required at the nuclear phase of the site, the nuclear phase distance can reach 70 meters, and is not affected by various conditions on the site, and all nuclear phase processes need only two people in two minutes. Can be completed within.

Wireless nuclear analyzer more features

The nuclear phase can be performed between two different voltage levels, either qualitatively (in phase, different phase) or quantitatively (phase angle difference between two power supply lines such as 30°, 60°, etc.).

The phase sequence was measured: positive phase sequence 120°, reverse phase sequence 240°.

Electrical inspection function: When the X or Y collector's acquisition head touches the live part of the high-voltage line or electrical equipment, if the line or equipment has power, the host displays X or Y.